Direct Vent Supplement
UMLA / UMLVA Oil Fired Warm Air Furnaces
INSTALLATION, OPERATION &
MAINTENANCE MANUAL
ALL INSTALLATIONS MUST MEET ALL LOCAL, PROVINCIAL/
STATE, AND FEDERAL CODES WHICH MAY DIFFER FROM THIS
MANUAL
WARNING
Fire, explosion, asphyxiation and electrical
shock hazard. Improper installation could
result in death or serious injury. Read this
manual and understand all requirements
before beginning installation.
!
NOTICE
Information contained in this manual pertains
to oil red direct vent furnaces equipped with
manufacturer provided and eld installed blocked
vent safety control system (pressure switch).
Manufactured by:
ECR International Inc.
2201 Dwyer Avenue, Utica, NY 13501
Tel. 800 325 5479
www.ecrinternational.com
PN 240011300 REV. G [10/01/2021]
2
PN 240011300, Rev. G [10/01/2021]
DIRECT VENT OIL FIRED WARM AIR FURNACE
ALL INSTALLATIONS MUST MEET ALL LOCAL, PROVINCIAL/STATE,
AND FEDERAL CODES WHICH MAY DIFFER FROM THIS MANUAL
Read and understand this manual before beginning
installation. Instructions must be kept with furnace
for future reference.
3
PN 240011300, Rev. G [10/01/2021]
WARNINGS AND SAFETY SYMBOLS
DIRECT VENT OIL FIRED WARM AIR FURNACE
1. DIRECT VENTING OF OLSEN OIL FIRED FURNACES ..................................................................... 4
2. VENT TERMINAL LOCATION ...................................................................................................... 5
3. VENT TERMINAL INSTALLATION ................................................................................................ 6
4. VENT TERMINAL RISER KIT ..................................................................................................... 6
5. DIRECT VENT INTAKE AIR PIPE INSTALLATION ........................................................................... 7
6. VENTING INSTALLATION - DIRECT VENT .................................................................................... 8
7. BLOCKED VENT SAFETY SWITCH PRESSURE TUBING CONNECTIONS. ............................................ 9
8. OIL BURNER SETUP ................................................................................................................10
9. FURNACE SET UP ADJUSTMENTS .............................................................................................14
10. BLOCKED VENT SAFETY SHUT OFF SYSTEM ..............................................................................14
11. SEQUENCE OF OPERATION .....................................................................................................14
12. FINAL CHECK OUT.................................................................................................................14
DIRECT VENTING WIRING DIAGRAM ............................................................................................15
DIRECT VENTING OF OLSEN OIL FIRED FURNACES - VENTING COMPONENTS ..................................... 16
VENTING COMPONENTS/MATCHING GUIDE ....................................................................................17
DIRECT VENT - PARTS IDENTIFICATION ........................................................................................17
BECKETT BURNER BLOCKED VENT SAFETY (BVS) OPERATION ..........................................................18
BECKETT BURNER TROUBLESHOOTING .........................................................................................19
RIELLO 40BF BLOCKED VENT SAFETY (BVS) OPERATION .................................................................21
RIELLO 40BF BURNER TROUBLESHOOTING ....................................................................................22
HOMEOWNER’S REFERENCE TABLE ...............................................................................................23
DANGER
Indicates a hazardous situation which, if not avoided,
WILL result in death or serious injury
!
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal
injury.
4
PN 240011300, Rev. G [10/01/2021]
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
1. DIRECT VENTING OF OLSEN OIL FIRED FURNACES
Installation shall be done by a “Qualied Installer".
“Qualied Installer” shall mean an individual who has been
properly trained or is a licensed installer.
The UML oil red furnaces with suxes NXU for Beckett's
NX , and RBU for Riello’s 40BF series oil burners, are
certied for venting through the wall using ducted outdoor
air for combustion.
The Direct Vent series is ideal for applications where a
conventional chimney is unavailable, nor easily installed;
an electrically heated home being retrot for oil forced air
heating for example.
The term Direct Vent refers to a sealed combustion
system.
Direct vented appliances require some foresight and
planning, since the range of ue lengths is restricted,
clearances are critical, and national and local codes are
quite strict with respect to safety. Be sure that the furnace
can be installed within the physical limitations of the
home, and in accordance with local codes and regulations.
Physical limitations include practical issues such as
sucient clearance to grade. It is advisable to install
the vent termination in an area sheltered from winter
prevailing winds. Avoid vent termination locations subject
to frequent strong wind gusts.
It is the installer's responsibility upon installation and the
user's responsibility during subsequent operation to ensure
that gases issuing from the vent terminal do not cause a
hazard through contact with adjacent naturally occurring
combustible materials.
It is the homeowner's responsibility to ensure the area
around the vent terminal and air intake is free of snow,
ice and debris. Check the vent terminal during heavy
snowstorms to ensure proper operation.
In extremely cold climates, ice may have to be removed
from the vent terminal on a regular basis.
B-VENT SHALL NOT BE USED IN THE VENT SYSTEM.
Figure 1 - Standard Vent Terminal Assembly
Oil Burners:
Beckett NX (
1
)
Riello 40BF
(
1
)Beckett NX oil burner is not approved for downow or
horizontal installation when burner is equipped with optional
burner cover.
Venting Materials and Fittings:
For approved components, see Figures 10-12.
2. VENT TERMINAL LOCATION
5
PN 240011300, Rev. G [10/01/2021]
Figure 2 - Vent Terminal Locations - Canada
The through the wall termination shall be installed in
accordance with the latest editions of CAN/CSA B-139
(Canada), NFPA-31 (United States), and / or any applicable
local codes.
Vent terminal can be installed in a wall having minimum
thickness of 5" and maximum thickness of 10".
Refer to Figure 2 below. In Canada, the vent terminal
shall not terminate:
A. Directly above a paved sidewalk or a paved driveway
that is located between two buildings, and that serves
both of them.
B. Less than 7 feet (2.13 m) above any paved sidewalk
or a paved driveway.
C. Within 6 feet (1.80 m) of a window, door, or
mechanical air supply inlet to any building, including
sot openings.
D. Above a gas / regulator assembly within 3 feet (1 m)
horizontally of the center-line of the regulator.
E. Within 6 feet (1.80 m) of any gas service regulator
vent outlet or within 3 feet (1 m) of any oil tank vent
or any oil tank ll inlet.
F. Less than 1 foot (0.3 m) above grade level within 6
feet (1.80 m) of any combustion air inlet, unless the
appliance is otherwise certied.
G. Within 6 feet (1.80 m) of the property line.
H. Underneath a verandah, porch, or deck.
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
I. So ue gases are directed at combustible material
or at any openings of surrounding buildings that are
within 6 feet (1.80 m).
J. Less than 3 feet (1 m) from an inside corner of an
L-shaped structure.
K. So that the bottom of the vent termination opening is
less than 1 foot (0.3 m) above any surface that may
support snow, ice, or debris.
L. So that the ue gases are directed towards bricks,
siding, or other construction, in such a manner that
may cause damage from heat or condensate from the
ue gas.
M. Within 4 feet (1.2 m) of a power venter.
6
PN 240011300, Rev. G [10/01/2021]
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
Figure 3 - Vent Terminal Locations - United States
Refer to Figure 3 below. In the United States, a vent
terminal shall not terminate:
Less than 7 feet (2.13 m) above any adjacent public
walkway.
Less than 4 feet (1.22 m) below, 4 feet horizontally, or 1
foot (0.3 m) above a door, window, or gravity air inlet of
the structure.
Less than 1 foot (0.3 m) above grade.
Less than 1 foot (0.3 m) from the sot of the roof of the
structure.
Less than 3 feet (0.9 m) from the inside corner of an L
shaped structure.
Less than 5 feet (1.6 m) from a gas regulator vent outlet,
or oil tank vent outlet.
3. VENT TERMINAL INSTALLATION
This applies to the standard 28972 Direct
Vent Oil Vent Terminal. See Figure 1.
Select the location of wall penetration that conforms to
the code for exterior location, as close to the appliance as
possible, maintains clearance to combustibles and where the
minimum 1/4-inch per foot slope back to the appliance can be
maintained.
Cut 6-1/2” diameter hole through the wall.
Remove the Intake Air Sleeve from the Terminal.
Insert Terminal through the wall from outside, secure
with 4 screws to the wall, seal to wall with weatherproof
sealant.
From inside the building, reattach the Intake Air Sleeve
and secure inner sleeve to outer sleeve with 2 screws.
Use 4 screws to secure Sleeve to the wall. Ensure the
Intake Air Connector is located for ease of attachment and
complies with code.
4. VENT TERMINAL RISER KIT
The 29231 Vent Terminal Riser Kit has been designed to
increase the height above grade level of the Vent Terminal
by approximately 3 feet. See Figure 5 for typical Vent Riser
setup. This is ideal where excessive snow build up could occur
or where more exibility is required to maintain minimum
clearances to grade.
7
PN 240011300, Rev. G [10/01/2021]
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
Figure 4 - Inside View of Vent Terminal
5. DIRECT VENT INTAKE AIR PIPE INSTALLATION
NOTICE
Flexible duct for combustion air use is not
permitted.
IMPORTANT: OUTDOOR AIR FOR COMBUSTION MUST BE
USED.
The oil burners approved for use with ducted outdoor air
for combustion are Beckett NX , Riello 40BF. All units obtain
outdoor air by the following means:
Acceptable combustion air intake materials:
1.
4-inch “C” Vent (single wall galvanized).
2.
4-inch Rigid Aluminum pipe (0.030” wall thickness).
3.
Beckett NX burners, are furnished with a 4” diameter
straight combustion air intake collar for connecting eld
supplied 4” combustion air intake pipe to the burner. The
intake collar is equipped with a hose tting for connecting
the negative pressure side of the blocked vent safety
switch (pressure switch).
4.
Riello 40BF3/BF5 burners are furnished with a 3” diameter
straight combustion air intake collar and a 3” diameter
90° elbow combustion air intake collar. Both intake
collars are equipped with hose ttings for connecting the
negative pressure side of the blocked vent safety switch
(pressure switch). Use whichever intake collar (straight
or elbow) is most convenient depending on the furnace
position (upow/downow/horizontal). Typically the elbow
must be used in upow installations to avoid the intake
air pipe interfering with the vent pipe. Riello burners are
also furnished with a 3” to 4” increaser tting and a 3"
diameter plain elbow (without hose tting). The increaser
tting connects to the intake collar for connecting eld
supplied 4” combustion air intake pipe to the burner. The
plain elbow is for other furnace models and is not used
with the UML.
IMPORTANT: Intake pipe and ttings should be sealed
with foil tape, duct tape, or silicone caulking and
attached mechanically with screws.
Figure 5 - Vent Riser
Maximum combustion air intake length is 25 feet using 8
90° elbows. Venting installation dictates the length from
termination cannot be further than 20 feet; therefore any
longer piping for combustion air intake would be unnecessary.
Combustion air intake does not have minimum length.
Condensation may become a problem during some climatic
conditions. It may be necessary to wrap a portion, or entire
intake piping (particularly metal intake piping) with waterproof
insulation material.
8
PN 240011300, Rev. G [10/01/2021]
CAUTION
Use appropriate safety precautions! Wear protective
gloves. Thin metal edges are extremely sharp if not
avoided, could result in minor or moderate injury.
7. BLOCKED VENT SAFETY SWITCH MOUNTING AND
PRESSURE TUBING CONNECTIONS
WARNING
Failure to properly install the blocked vent safety
switch could result in death or serious injury.
!
The blocked vent safety switch and associated pressure switch
tubing are shipped loose with the furnace. The pressure
switch must be mounted in the correct location on furnace ue
collar, which varies depending on furnace orientation (upow/
downow/horizontal). See Figure 7.
Conrm the pressure switch is part number 240011288
with 0.50" W.C. set point.
Mount the pressure switch in the correct location on the
ue collar assembly according to Figure 7 using two #8
x ½” sheet metal screws provided with the switch. See
Figure 6.
Connect the 6.5” long black high temperature tubing
from the positive pressure port (the black port) on the
pressure switch to the hose barb on the appliance vent
adapter. If the appliance vent adapter and pressure switch
are properly located, the 6.5” tubing should be just long
enough to be installed with no dips or sags. It should be
uphill all the way to the pressure switch. This prevents
condensation from collecting in the tubing. See Figure 7.
Connect the 30” grey pressure switch tubing from the
negative pressure port (the grey port) on the pressure
switch to the hose tting on the burner combustion air
intake pipe. This tubing can be cut shorter if desired for
convenience. It is not necessary to avoid dips or sags with
this tubing. See Figure 7.
Connect the two yellow low voltage wires from the burner
to the pressure switch terminals.
Figure 6 - Pressure Switch Mounting
6. VENTING INSTALLATION - DIRECT VENT
VENT CLEARANCE TO COMBUSTIBLES: ONE (1) INCH.
WARNING
Fire, asphyxiation hazard. Do not enclose vent.
Do not route vent through walls, oors or ceilings.
Improper installation could result in death or serious
injury.
!
INSTALLATION OF "INSULATED DOUBLE WALL FLEXIBLE
VENT”.
The inner pipe is constructed of 4 inch 316 stainless steel, with
a two-ply aluminum outer pipe. High temperature insulation
separates the inner and outer ex pipes. Refer to Figure 10.
IMPORTANT: The venting and vent terminal are
dedicated to the furnace only; do not attempt to vent
any other appliance through it.
Install venting as follows. Installation shall comply with
CAN/CSA B139 Installation Code for Oil Burning Equipment
(Canada) or NFPA 31 Standard for Installation of Oil Burning
Equipment (United States), and / or with local codes and
regulations.
A. In as short and straight a run as possible without any
unnecessary bends.
B. There should not be any dips or sags throughout the full
length of vent.
C. Connector or vent should be sloped upwards from the
appliance at least 1/4” per foot.
D. Do not bend the connector or vent more than 90
degrees.
E. Vent may be cut to minimum of 5 feet in length using
ne tooth (24 teeth per inch) hacksaw blade.
F. Male and female ends of appliance adapters and
connectors must be cleaned with residue free brake
cleaner solvent.
G. Apply minimum 1/4” bead of Si-Ultra Copper Sealant
provided, onto outside of male end of vent to appliance
connector. Fit connector to vent by threading it counter-
clockwise until it stops. Ensure joint is not cross-
threaded.
H. IMPORTANT: The orientation of the appliance
adapter (where vent pipe connects to furnace) is
critical to correct operation of the blocked vent
safety switch. Apply minimum ¼” bead of same
sealant as mentioned above onto female end inside of
appliance connector. Slip connector over end of furnace
ue collar until it stops. Orient the combustion sample
test port and pressure switch hose tting per Figure 7
according to the furnace position. Tighten attached gear
clamp.
I. Support Vent every 36” to prevent sagging.
J. Attach Terminal Connector as described in steps G and H
listed above.
K. Maximum vent length is 20 feet (using a 20 foot vent
kit) Piecing vent kits together (i.e. using 2 ten foot kits
is strictly prohibited).
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
!
Pressure Switch
(PS) Mounted
on top of ue
collar assembly -
Upow position
9
PN 240011300, Rev. G [10/01/2021]
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
Figure 7 - Appliance Adapter Orientation, Pressure Switch Location, and Tubing Connections for Proper
Blocked Vent Safety Switch Operation
240011289
Appliance Adapter
Mounted on Flue Collar
Assembly
Test Port On
240011289
Appliance Adapter
Pressure Switch
(PS) Mounting
Location on Flue
Collar Assembly
Black Pressure
Tubing To
Appliance
Adapter
Grey Pressure
Tubing To
Combustion Air
Intake Collar
Combustion
Air Intake
Collar
D o w n o w
Test Port at 9:00
U p o w
Test Port at 12:00
PS
Horizontal
Right
Test Port at 12:00
Horizontal
Left
Test Port at 9:00
10
PN 240011300, Rev. G [10/01/2021]
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
8. OIL BURNER SET UP
Shut o electrical power to the furnace.
Install an oil pressure gauge to the pressure port on the oil
pump.
Set up the burner for initial ring as indicated in:
º Chart 1 for Beckett NX burners
º Chart 2 for Riello 40BF burners
Refer to oil burner instructions provided with furnace
documents envelope for specic information concerning
burner adjustment, operation and troubleshooting.
See gure 8, or 9 as applicable for proper air adjustment
technique.
Restore electrical power to furnace.
Start the furnace and bleed all air from fuel oil lines.
Close purge valve and re the unit.
Allow the furnace to warm up to normal operating
temperatures. During this time set the pump pressure in
accordance with Chart 1 or 2 as applicable.
Combustion must be checked with intake air piping
connected for 100% outdoor combustion air to burner.
Length of intake air piping and outside air temperature will
aect the combustion readings.
º For Riello burners the standard burner cover must be in
place on the burner to insure 100% outdoor air.
º For Beckett NX burners, the intake air pipe is
congured such that 100% outdoor air is achieved
either with or without optional burner cover.
Determine the Desired CO2 Setpoint:
º Combustion air temperature variations will aect how
much air enters the burner. Colder air is denser, so
contains more air per unit volume. More air enters the
burner when the combustion air is cold. Combustion
air temperature must be taken into consideration when
setting up the burner to account for these variations.
º When the furnace has reached steady state (after
approximately 10-15 minutes), remove the bolt from
the test port in the appliance connector. Set the
combustion air to obtain a TRACE of smoke.
º Using suitable combustion test instruments, measure
the Trace Point CO2 at the test port.
º Calculate CO2 Setpoint A = Trace Point CO2 minus
1.5% and enter it here:
Setpoint A: _______________
EXAMPLE: Assume Trace Point CO2 = 13.0%
Setpoint A = Trace Point CO2 minus 1.5% = 13.0%
minus 1.5% = 11.5%
º Measure the incoming combustion air temperature.
º Using Chart 3, determine Setpoint B for the measured
incoming combustion air temperature (choose the
midpoint of the range) and enter it here:
Setpoint B: ________________
Figure 8 - BECKETT NX AIR/HEAD SETTING
Loosen splined nut on nozzle line about one turn.
Turn air adjustment screw clockwise to increase air and
counter clockwise to decrease air.
Retighten splined nut after obtaining proper settings.
º The Desired CO2 Setpoint is the lower of Setpoint A or
Setpoint B. Enter it here:
Desired CO2 Setpoint: _____________________
Open the air setting to introduce additional excess air to
reduce CO2 to the Desired CO2 Setpoint.
Smoke reading should be ZERO. If not, increase air to
obtain ZERO smoke.
Lock the air setting.
Recheck smoke and combustion.
11
PN 240011300, Rev. G [10/01/2021]
To adjust the initial air damper setting, remove the burner
cover and turn the air damper adjustment screw (2)
until the top edge of the air damper (3) is in line with the
corresponding number from Chart 2.
Further adjustments must be made with the burner cover
in place by removing the plastic plug on the cover.
Turn the screw clockwise to increase combustion air or
counter clockwise to decrease combustion air.
When proper combustion and smoke spot readings are
achieved, reinsert plastic cap over air adjustment hole.
Figure 9 - RIELLO 40BF AIR DAMPER
NOTICE
Variations in CO2, smoke and temperature readings
will be experienced with Riello burners when burner
cover is in place. Burner cover must be in place
when making measurements to ensure proper test
results.
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
12
PN 240011300, Rev. G [10/01/2021]
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
Beckett NX Series Oil Burners
(For use with direct vent units using outdoor combustion air only.)
Furnace Model
Output
[BTU/Hr]
Burner
Model
Delavan
Nozzle
Pump
Pressure
[PSIG]
Flow Rate
[USGPH]
Low Firing
Rate Bae
Air
Setting
UML65ANXU
65,000 NX56LQ 0.50/60°W 140 0.55 Yes 3
UMLV65ANXU
UML80ANXU
76,000 NX56LQ 0.50/60°W 175 0.65 Yes 3.25
UMLV80ANXU
UML90ANXU
86,000 NX56LQ 0.60/60°W 175 0.75 No * 3.25
UMLV90ANXU
UML100ANXU
97,000 NX56LQ 0.65/60°W 175 0.85 No * 3.75
UMLV100ANXU
* Burner is factory equipped with low ring rate bae. Remove as shown for 0.75 and 0.85 USGPH ring rates.
Riello 40BF3/40BF5 Series Oil Burners
(For use with direct vent units using outdoor combustion air only.)
Furnace Model
Output
[BTU/Hr]
Burner
Model
Delavan
Nozzle
Pump
Pressure
[PSIG]
Flow Rate
[USGPH]
Turbulator
Setting
Air
Setting
UML65ARBU
65,000 40BF3 0.50/90°B 125 0.55 0.0 4.25
UMLV65ARBU
UML80ARBU
76,000 40BF3 0.55/80°B 140 0.65 1.0 5.25
UMLV80ARBU
UML90ARBU
86,000 40BF5 0.65/80°B 140 0.75 0.0 3.75
UMLV90ARBU
UML100ARBU
97,000 40BF5 0.75/80°B 130 0.85 0.0 4.25
UMLV100ARBU
Chart 1 - Beckett NX Oil Burner Setup
Chart 2 - Riello 40BF Oil Burner Setup
Note: Riello 40BF3 burner is required for 0.55 and 0.65 USGPH ring rates. Riello 40BF5 burner is required for 0.75
and 0.85 USGPH ring rates.
13
PN 240011300, Rev. G [10/01/2021]
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
Incoming
Combustion Air
Temperature at
Burner °F
Desired
CO2%
Range
-20 9.9 - 10.5
-10 10.1 - 10.7
0 10.4 - 11.0
10 10.6 - 11.2
20 10.9 - 11.5
30 11.1 - 11.7
40 11.4 - 12.0
50 11.7 - 12.3
60 11.9 - 12.5
70 12.2 - 12.8
80 12.4 - 13.0
90 12.7 - 13.3
Chart 3 - CO2 Setting Versus Incoming Combustion Air Temperature
to Achieve Approximately 20% Excess Air at 70°F Incoming Combustion Air Temperature
14
PN 240011300, Rev. G [10/01/2021]
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
10. BLOCKED VENT SAFETY SHUT OFF SYSTEM
Each direct vent furnace is equipped with a Blocked Vent
Safety shut o system (BVS). This safety circuit will shut the
burner o in the event of a combustion air blockage or venting
blockage.
The components of this BVS consist of a pressure switch. The
BVS is wired in series with the low voltage T-T connection on
the oil primary control.
11. SEQUENCE OF OPERATION
1.
Room temperature drops, thermostat calls for heat.
2.
Pre-purge begins, lasting 5 to 15 seconds.
3.
Oil solenoid energized
4.
Oil Solenoid opens allowing oil to reach the Burner
Electrodes. Burner ignition begins.
5.
Cad cell detects light from combustion, disconnects the
primary control safety circuit, allowing combustion to
continue.
6.
After 15 to 45 seconds (depending on primary control
characteristics), the electric spark across the electrode tips
stops, combustion continues.
7.
The furnace blower will start after the programmed fan
on delay as determined by the dipswitch settings on the
electronic fan timer control.
8.
Furnace continues to operate and will eventually reach
"steady state", the point at which the system temperature
stabilizes.
9.
Room temperature rises, thermostat is satised, heating
contacts open.
10.
Oil Solenoid Valve closes, combustion stops, Burner Motor
remains on to complete the Post Purge Cycle. Post Purge
will continue up to 6 minutes depending on the control
switch settings. Factory post purge setting is 30 seconds.
This is recommended setting for typical applications.
11.
The furnace blower will stop after the programmed fan
o delay as determined by the dipswitch settings on the
electronic fan timer control.
12.
Furnace remains idle until next call for heat.
12. FINAL CHECK OUT
Before nal test cycle, carefully examine complete vent system
for leaks.
Verify all safety devices and electrical components have been
set for normal operation. Verify all electrical connections are
tight and wiring is secure.
IMPORTANT: Ensure homeowner is informed and
understands:
1.
where circuit breaker or fuse is located in main electrical
panel.
2.
where furnace switch is located, and switch "on" and "o"
positions if not obvious.
3.
where oil shut-o valve from oil storage tank is located.
4.
to keep area around vent terminal free of snow, ice, and
debris.
5.
how to operate thermostat, and other related accessories.
6.
how to operate manual reset button on primary control,
and when not to push reset button.
7.
how and where to visually inspect venting system for leaks
or other problems.
8.
how to inspect, clean and replace air lter, and other
homeowner maintenance procedures.
9.
who to call for emergency service and routine annual
service.
10.
terms and conditions of manufacturer's warranty and
contractor's warranty.
9. FURNACE SET UP ADJUSTMENTS
Refer to Installation, Operation and Maintenance Manual
provided with furnace for specic set up instructions. See
Appendix A - Check Out and Adjustments, Section A.3 - Start
U P.
15
PN 240011300, Rev. G [10/01/2021]
LEGEND/legende
FACTORY WIRING
filage a l'usine
FIELD WIRING
filage au champs
TERMINAL PROVIDED/
point de raccord fourni
GROUND/Terre
TERMINAL NOT PROVIDED/point
de raccord non-fourni
120 V
24 V
24 V
120 V
240011184 REV D
BK BLACK/noir
BL BLUE/bleu
BR BROWN/brun
GR GREEN/vert
OR ORANGE/orange
RD RED/rouge
AUXILIARY LIMIT
LIMIT/limite
LOW SPEED FAN SWITCH (PSC BLOWER ONLY)
CAP CAPACITOR/capaciteur
YL YELLOW/jaune
WH WHITE/blanc
GND GROUND/Terre
VI VIOLET/violet
BLOCKED VENT SAFETY
limite auxiliaire
AL
interupteur a basse vitesse (CFP seulement de soufflante)
F
L
commande d'ûpreuve de système d'ûvacuation bloquû
BVS
transformateur d'allumage
IGNITER/
I
soupappe
VALVE/
V
L1
(FUSED DISCONNECT ON HOT LEG)
POWER SUPPLY 120 VAC 60 HZ
alimentation 120 VAC 60Hz
(disjoincteur avec fusible sur le fil d'alimentation)
C
R
W YG
THERMOSTAT
THERMOSTAT CONNECTIONS/
raccorde du thermostat
YG RW C
1158-1
CONTROL
BR
BR
CAP
WH
BK
N (COMMON)
GND
YL
YL
BURNER
MOTOR
1 2 43 53
UNUSED
12
EAC
CONT
HEAT
COOL
6
7
HUM
X
C
F
TRANSFORMER/
MHI
31 2 54
H
C
L
ML
N
WH
BK
BL
BR
WH
BK
VI
1
2
4
3
BK
WH
RD
RD
BL
120V
24V
24V
COM
GR
BVS
L
BLOWER
ventilateur
principale
INDOOR
moteur
MOTOR
BURNER MOLEX
CONNECTOR/
connecteur molex
du br�leur
transformateur
1158-1 / 1168-1
CONTROL
L1
YL
2
4
7
5
9
6
3
8
10
1
12
11
BL
BR
BR BR
CONTROL BOX
MOLEX CONNECTOR
Boîtier de commande
du connecteur Molex
AL
T-T
RD
RD
VI
WH
BK
RD
THERMOSTAT CONNECTIONS/
raccorde du thermostat
THERMOSTAT
G
Y/Y2
Y1
Y1 G
Y/Y2
C
R
W
O
DH
WODH
R
C
1168-1
CONTROL
INDOOR
ventilateur
principale
BLOWER
MOTOR
moteur
1
ECM
4 52 3
ventilateur a ECM
(si disponible)
ECM MOTOR
(IF AVAILABLE)
P1
16 1415
8 7 6
13
5
11
43
12 10 9
21
5
13
15 14
6
7
P1
8
16
12
91 012
34
11
CONTROL
1168-1
120 VAC
BK
NEUT
WH
YL
56
JUMPER *
BK
65
3421
BK
WH
BL
BR
CAP
9
11
7
8
BR
BK
WH
WH
6
3
2
1
530SEC
L
N
WH
moteur
MOTOR
V
BL
RD
WH
RD
GY
YL
BL
AL 1009
12
BL
RD
/ 24V
BK
VI
T
T
BL
YL
RIELLO BF3 BURNER/br�leur
(IF AVAILABLE)/(si disponible)
VI
BK
WH
L2 (WHITE)
IGNITER (BLUE/WHITE)
(YELLOW)
FLAME SENSOR
sonde a flame
VI
BL
OR
WH
BK
YL
YL
BECKETT BURNER/br�leur
moteur
MOTOR
V
I
BECKETT OIL
PRIMARY
CONTROL
L2 (WHITE)
L2 (WHITE)
VALVE (VIOLET)
MOTOR (ORANGE)
LIMIT (RED)
L1 (BLACK)
L2 (WHITE)
CAD CELL
WH
WH
WH
TR
TW
12
4356
TO T-T
BL
YL
YL
TO T-T
YL
BVS
DIRECT VENTING WIRING DIAGRAM
DIRECT VENTING WIRING DIAGRAM
16
PN 240011300, Rev. G [10/01/2021]
DIRECT VENTING OF OLSEN OIL FIRED FURNACES - VENTING COMPONENTS
Figure 10 - VENTING COMPONENTS
17
PN 240011300, Rev. G [10/01/2021]
VENTING COMPONENTS/MATCHING GUIDE
Figure 11 - Z-FLEX VENTING COMPONENTS / MATCHING GUIDE
Also included with vent kits:
Tube of Ultra Copper Sealant
4" Vent Terminal Connector Part Number 240006914
Also included with burners, as applicable:
Combustion Air Intake Collar, 4" Straight for Beckett burner Part Number 109005950
Combustion Air Intake Collar, 3" Straight for Riello burner Part Number 109006030
Combustion Air Intake Collar, 3" Elbow for Riello burner Part Number 3002333
Combustion Air Intake Increaser, 3" x 4" for Riello burner Part Number 240011310
Figure 12 - DIRECT VENT PARTS IDENTIFICATION
5”
Also included with furnace:
Blocked Vent Safety Switch (Pressure Switch) Part Number 240011288
(0.50" W. C . S e t Point f o r u s e w i t h B e ck e t t a n d Ri el l o B ur n er s )
6.5" of Black Pressure Switch Tubing Part Number 30705
30" Grey Pressure Switch Tubing Part Number 11344
Z-FLEX VENTING COMPONENTS MATCHING GUIDE
MODEL
ITEMS INCLUDED WITH
FURNACE
REQUIRED ITEMS ORDERED SEPARATELY
FIELD
SUPPLIED
COMPONENTS
TEMINATION STD OR RISER YOUR CHOICE OF
ITEM P/N ITEM P/N ITEM P/N
UML
5" X 4"
APPLIANCE
ADAPTER
240011289
OIL VENT
TERMINAL
28972 4" X 10' VENT KIT 240006909
COMBUSTION
AIR PIPING
OR 4" X 15' VENT KIT 240006910
OIL VENT
RISER
29231 4" X 20' VENT KIT 240006911
18
PN 240011300, Rev. G [10/01/2021]
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
EXTERNAL ACTION APPLIANCE RESPONSE
Power applied to 7505P control
Internal safety check conducted. If no light or ame is detected and all internal conditions are
correct, control enters idle mode.
Thermostat calls for heat.
1.
Contacts between T and T on 7505P are closed.
2.
Primary Control Safety period (4 seconds) internal and external check for ame or light. If
ame is detected, control remains in idle mode.
3.
When ame is not present, 7505P will apply power to the burner motor and igniter, complete a
15 second valve on delay period and then apply power to the oil valve circuit.
4.
Enters the trial for ignition period.
A. Monitors burner for ame.
B. When ame is not detected:
i. Enters lockout mode after 15 seconds.
ii. Shuts o valve, igniter and burner motor.
iii. Flashes indicator light at 1 Hz (½ second on, ½ second o).
iv. Depress reset button to return to power up sequence.
C. When ame is detected, Carry-Over period begins:
5.
Enters 10-second Ignition Carry-Over period.
A. Turns on indicator light
B. If ame is lost and lockout time has not expired, THE PRIMARY CONTROL returns to trial for
Ignition period.
C. If ame is lost and lockout time has expired, THE PRIMARY CONTROL enters Recycle Mode.
6.
Carry-over time expires and igniter turns o.
7.
Enters a run mode:
A. Flame is monitored until call for heat ends or ame is lost. If ame is lost:
i. Control enters Recycle Mode.
ii. Recycle time starts (60 seconds).
iii. Burner and valve are turned o.
iv. Red Light FlashSafety Lockout
Red Light SolidHard Lockout
v. Returns to Idle mode at end of Recycle mode.
Call for heat is satised.
1.
Oil valve circuit is de-energized and valve shuts o.
2.
Burner motor runs for selected burner motor-o delay.
3.
Burner motor turns o.
Returns to Idle mode
Reset button pushed two times
without device completing a call for
heat.
1.
Enters restricted Hard Lockout.
2.
Indicator light on continuously
3.
Reset device by pressing and holding reset button for a minimum of 15 seconds. (Yellow Light
Turns ON)
Pressure switch contacts open and
cause burner to recycle
In the event of vent or combustion air intake blockage, the blocked vent safety switch
(pressure switch) contacts will open, opening the contacts between T and T on the
7505P primary control, as if ending the call for heat. Once the post purge period (burner
motor o delay) ends, the burner motor will shut o and the pressure switch contacts
will re-close, again closing the T-T contacts and starting the burner motor. If the vent or
combustion air intake blockage remains, the pressure switch contacts will open again once
the burner motor is running, and shut the burner motor o. Continuous cycling of this type
indicates vent or combustion air intake blockage.
Figure 13 - BECKETT BURNER WITH BLOCKED VENT SAFETY (BVS) OPERATION
19
PN 240011300, Rev. G [10/01/2021]
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
Condition 1: Burner motor does not start when there is a call for heat.
Procedure Status Corrective Action
1. Check that limit switches are closed and contacts are
clean.
N/A N/A
2. Check for line voltage power at the oil primary control.
Voltage should be 120 Vac between the black and white
lead wires on the oil primary control.
N/A N/A
3. Check indicator light with burner o, no call for heat (no
ame).
Indicator light is
on.
Cad cell is defective, sees external light, or connections have
shorted. Go to step 4.
Indicator light
is o.
Go to step 5.
4. Shield cad cell from external light.
Indicator light
turns o.
Eliminate external light source or permanently shield cad
cell.
Indicator light
stays on.
• Replace cad cell with new cad cell and recheck.
• If indicator light does not turn o, remove cad cell lead
wires from and recheck.
• If indicator light is still on, replace control.
• If the indicator light turns o, replace cad cell bracket
assembly.
5. Verify that the oil valve is closed during the “valve on
delay” period by observing the view port and verifying that
no ame is present during the 15-second “valve on delay”.
Indicator light
is on.
If ame is present, replace the oil valve.
6. Conrm BVS pressure switch contacts closed.
Contacts closed
- Go to step 7
Contacts open - Replace BVS pressure switch
7. Jumper thermostat (T -T) terminals on 7505P
IMPORTANT
First remove one thermostat lead wire.
Burner starts.
Trouble is in thermostat circuit. Check thermostat-wiring
connections.
If connections are clean and tight, check thermostat wires
for continuity.
Burner does not
start.
• Disconnect line voltage power and open line switch.
• Check all wiring connections.
• Tighten any loose connections and recheck.
• If burner still doesn't start, replace 7505P.
If burner still doesn't start, check the oil burner motor. It
may be seized or burned out.
Figure 14 - BECKETT BURNER TROUBLESHOOTING
20
PN 240011300, Rev. G [10/01/2021]
Condition 2: Burner starts then locks out on safety with indicator light ashing at 1/2 second on, 1/2 second o.
Procedure Status Corrective Action
1. Reset oil primary control by pushing in and releasing red
reset button. Flash - 1 sec. / Solid - 1 sec.
Indicator light
stops ashing.
Go to Step 2.
Indicator light
continues to ash
at 1/2 second on,
1/2 second o
rate.
Verify that the control is not in restricted mode. (See notes
at end of this table.). If not in restricted mode, replace
7505P
2. Listen for spark after burner turns on (after 2 second
delay).
Ignition is o
Spark igniter could be defective. Check for line voltage at
igniter terminals. If line voltage is present, replace 7505P.
Ignition is on.
Go to Step 3.
Ignition is on but
no oil is being
sprayed into
the combustion
chamber.
Wait for “Valve ON” delay to complete.
1. Check oil supply.
4. Check oil line valve.
5. Check for lter blockage or seized oil pump.
3. Check indicator light after ame is established, but
before oil primary control locks out.
Indicator light
is on until the
control locks
out and starts
ashing during
lockout.
Replace 7505P
Indicator light
stays o.
Go to step 4.
4. Check cad cell sighting for view of ame.
a. Disconnect line voltage power and open line switch.
b. Unplug cad cell and clean cad cell face with soft cloth.
Check sighting for clear view of ame. Replace cad cell in
socket.
c. Reconnect line voltage power and close line switch.
d. Start burner.
Burner locks out Go to step 5.
Burner keeps
running.
System is OK.
5. Check cad cell.
a. Disconnect line voltage power and open line switch.
b. Remove existing cad cell and replace with new cad
cell.
c. Disconnect all wires from thermostat terminals to
ensure that there is no call for heat.
d. Reconnect line voltage power and close line switch.
e. Expose new cad cell to bright light such as a
ashlight.
Indicator light
is on.
Remount control onto burner housing, go to step 6.
Indicator light
is o.
System is OK.
6. Check cad cell bracket assembly.
a. Disconnect line voltage power and open line switch.
b. Remove cad cell wires from quick connect connectors
on the R7505P and leave control lead wires open.
c. Apply power to device.
d. Place jumper across cad cell terminals after
Indicator light
is on.
Replace CAD cell bracket assembly.
Indicator light
is o.
Replace 7505P
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
NOTE: Hard Lockout : In order to limit the accumulation of unburned oil in the combustion chamber, the control can be reset only 5 times,
after which, the control locks out. The reset count returns to zero each time a call for heat is successfully completed.
To reset from Hard Lockout: press and hold the reset button for 15 seconds. When the Yellow LED ashes turns on, the device has reset.
NOTE: Disable function: Pressing and holding the reset button will disable all functions until the button is released. The burner will restart at
the beginning of the normal heat cycle on SAFETY CHECK.
Figure 14 - BECKETT BURNER TROUBLESHOOTING - continued
Condition 3: Burner motor continuously cycles on and o without trying to light burner.
- Blocked vent safety switch (pressure switch) contacts opening each time burner motor starts
- Check venting for blockage
- Check combustion air intake air pipe for blockage
- Check pressure switch hoses for possible obstruction
21
PN 240011300, Rev. G [10/01/2021]
EXTERNAL ACTION APPLIANCE RESPONSE
Thermostat calls for heat.
1. Contacts between T and T on oil burner primary control are closed.
2. Burner enters pre-purge.
3. After pre-purge, oil valve is energized and burner lights o.
4. Burner operates in run mode.
Call for heat is satised.
1. Oil valve circuit is de-energized and valve shuts o.
2. Burner motor runs for duration of burner motor-o delay.
3. Burner motor turns o.
Pressure switch contacts open and cause
burner to re-cycle
In the event of vent or combustion air intake blockage, the blocked vent safety switch (pressure
switch) contacts will open, opening the contacts between T and T on the oil burner primary
control, as if ending the call for heat. Once the post purge period (burner motor o delay) ends,
the burner motor will shut o and the pressure switch contacts will re-close, again closing the
T-T contacts as if calling for heat and starting the burner motor as described above. If the vent
or combustion air intake blockage remains, the pressure switch contacts will open again once the
burner motor is running, and shut the burner motor o. Continuous cycling of this type indicates
vent or combustion air intake blockage.
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
Figure 15 - RIELLO 40BF With BLOCKED VENT SAFETY (BVS) OPERATION
22
PN 240011300, Rev. G [10/01/2021]
Condition: Thermostat is calling for heat. Burner is not running.
Problem Possible Cause
Remedy
1. Reset control box.
Burner starts. Go to step #4.
Burner does not start Go to step #2
2. Test for 120 Vac supply at sub-base
between L (P) & N or terminals #3 and
#5.
120 Vac present. Go to step #3
No voltage
• Check system fuse, breaker or ensure service
switch is ON.
• Verify all limits are closed.
• If using switching relay, verify 24 Vac at T-T.
3. Conrm BVS pressure switch contacts
closed.
Contacts Closed Go to step #4
Contacts Open Replace BVS
4. Turn o power supply- Remove control
box and jumper terminals #5 and #6.
Restore power.
Motor runs.
• Verify reduced voltage (42-52 Vac) between
terminals #3 and #7.
• Ensure good contact between control box
spades and sub-base terminals.
• Defective control box/ Replace.
Motor does not run.
• Verify electrical connections.
• Check for seized pump, motor, or fan against
housing.
• Defective motor capacitor.
• Thermal overload (Hot motor).
5. Burner Starts
Burner stays in Pre-purge.
• Faulty CAD cell or seeing light before trial for
ignition.
• Coil wires on terminals #1 and #2 or #1 and
#8 reversed.
• Open coil circuit; terminals #2 and #8.
• Open coil circuit; terminal #1
• Defective 42-52 Vac supply, terminals #3 and
#7.
• Defective control box/ Replace
Burner continues to purge and light o with
immediate ame dropout.
• Metal yoke for coil missing.
• Coil wire #2 and #8 reversed.
• Low resistance of coil holding circuit,
terminals #1 and #2, (1350 ohms ± 10%)..
• Verify BVS pressure switch is remaining closed
upon light o.
Burner locks out after trial for ignition.
• Low resistance or no contact on starting
circuit of coil, terminals #2 and #8. (1.3-ohm
± %)
• No oil supply- tank empty, valve closed, dirty
lter, damaged supply lines.
• Defective or dirty oil valve stem, nozzle, or
pump strainer.
• Broken pump drive key, defective pump or no
oil pressure.
• Ignition electrodes shorted, cracked porcelain.
• Burner motor not up to speed.
• Excessive draft over re.
• Defective control box/ Replace.
6. Burner motor continuously cycles on
and o without trying to light the burner.
Blocked Vent Safety Switch (Pressure Switch)
Opening
Check venting for blockage
Check combustion air intake pipe for blockage
Check pressure switch operation. Conrm
contacts closed when furnace not running.
Check pressure switch tubes for possible
obstruction
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
Figure 16 - RIELLO 40BF BURNER TROUBLESHOOTING
23
PN 240011300, Rev. G [10/01/2021]
DIRECT VENTING OF OLSEN OIL FIRED FURNACES
HOMEOWNER’S REFERENCE TABLE
Model No.
Serial No.
Date Installed
Contractor
Contact
Address
Postal Code
Telephone No.
After Hours No.
FUEL SUPPLIER
Fuel Oil Supplier
Contact
Telephone No.
After Hours No.
IF DIFFERENT FROM INSTALLATION CONTRACTOR:
Service Tech.
Telephone No.
After Hours No.
All specications subject to change without notice.
©2021 ECR International, Inc.
2201 Dwyer Avenue, Utica, NY 13501
Tel. 800 325 5479
www.ecrinternational.com